When the mains power is available, the UPS will alarm when the mains power is cut off
Possible causes:
The mains input air switch trips;
Poor contact of input AC line;
The mains input voltage is too high, too low or the frequency is abnormal;
UPS input air switch or switch is damaged or fuse is blown;
UPS internal mains power detection circuit failure.
processing method
Check the input air switch. Check the input line;
If the mains supply is abnormal, do not handle or start the generator to supply power;
Replace the damaged air switch, switch or fuse;
Check UPS mains power detection circuit.
2 When the mains power is normal, the UPS output is normal; After the mains power is cut off, the load is also cut off
Possible causes
The battery is under voltage due to the low voltage of the mains supply;
The UPS charger is damaged and the battery cannot be charged;
Battery aging and damage;
Load overload, UPS bypass output;
Load is not connected to UPS output;
The battery pack of the long delay model is not connected or has poor contact;
UPS inverter is not started (UPS panel control switch is not opened), and the load is powered by mains bypass;
The inverter is damaged, and UPS bypass output.
processing method
Fully charge the battery when the mains voltage is normal; Start the generator to charge the battery; Add voltage stabilizer at UPS input end;
Check the charger. Replace the battery;
Reduce the load. Connect the load to the output of UPS;
Check whether the battery pack is connected correctly;
Start the inverter to supply power to the load (open the panel control switch);
Check the inverter.
3 UPS fails to start
Possible causes
The battery is not used for a long time, and the voltage is low;
Input AC and DC power lines are not connected properly;
UPS internal startup circuit fault;
UPS internal power circuit fault or power short circuit;
The power components inside the UPS are damaged.
processing method
Fully charge the battery;
Check whether the input AC and DC lines are in good contact;
Check the UPS power on circuit;
Check the UPS power circuit;
Check whether the components in the rectifier, booster, inverter and other parts of the UPS are damaged.
4 When UPS is started, input air switch trips
Possible causes
The input air switch capacity is too small;
UPS internal short circuit;
The power components inside the UPS are damaged;
The utility air switch of the user is provided with leakage protection.
processing method
Replace the input air switch;
Check whether the components in the rectifier, booster, inverter and other parts of the UPS are damaged;
Check whether the components in the rectifier, booster, inverter and other parts of the UPS are damaged;
Replace with air switch without leakage protection.
5 When UPS is in normal use, a long buzzer alarm suddenly appears
Possible causes
The user starts with heavy load or heavy impact load;
Sudden short circuit at the output end;
UPS internal inverter circuit fault;
UPS protection and detection circuit malfunction.
processing method
The load shall be put into operation in the order of first large and then small; Increase the power capacity of UPS;
Check whether the output of UPS is short circuited;
Check the UPS inverter. Check the UPS internal control circuit.
6 UPS works normally but load equipment is abnormal
Possible causes
UPS output zero ground voltage is too high;
UPS ground wire and load equipment ground wire are not connected at the same point;
The load equipment is subject to abnormal interference.
processing method
Check the UPS grounding. If necessary, connect a 1-3K Ω resistance between the zero and ground of the UPS output terminal;
Connect UPS ground and load ground to the same point;
Restart the load device.